Rating
Generators must be capable of delivering the power required for the hours per year anticipated by the designer to allow reliable operation and prevent damage. Typically a given set can deliver more power for fewer hours per year, or less power continuously. That is a standby set is only expected to give its peak output for a few hours per year, whereas a continuously running set, would be expected to give a somewhat lower output, but literally continuously, and both to have reasonable maintenance and reliability.
To meet the above criteria manufactures give each set a rating based on internationally agreed definitions.
These standard rating definitions are designed to allow correct machine selection and valid comparisons between manufacturers to prevent them from misstating the performance of their machines, and to guide designers
Wednesday, September 9, 2009
Generator Rating Definitions
Standby Rating based on Applicable for supplying emergency power for the duration of normal power interruption. No sustained overload capability is available for this rating. (Equivalent to Fuel Stop Power in accordance with ISO3046, AS2789, DIN6271 and BS5514). Nominally rated.
Typical application - emergency power plant in hospitals, offices, factories etc. Not connected to grid.
Prime (Unlimited Running Time) Rating based on: Applicable for supplying power in lieu of commercially purchased power. Prime power is the maximum power available at a variable load for an unlimited number of hours. A 10% overload capability is available for limited time. (Equivalent to Prime Power in accordance with ISO8528 and Overload Power in accordance with ISO3046, AS2789, DIN6271, and BS5514). This rating is not applicable to all generator set models.
Typical application - where the generator is the sole source of power for say a remote mining or construction site, fairground, festival etc.
Base Load (Continuous) Rating based on: Applicable for supplying power continuously to a constant load up to the full output rating for unlimited hours. No sustained overload capability is available for this rating. Consult authorized distributor for rating. (Equivalent to Continuous Power in accordance with ISO8528, ISO3046, AS2789, DIN6271, and BS5514). This rating is not applicable to all generator set models
Typical application - a generator running a continuous unvarying load, or paralleled with the mains and continuously feeding power at the maximum permissible level 8760 hours per year. This also applies to sets used for peak shaving /grid support even though this may only occur for say 200 hour per year.
As an example if in a particular set the Standby Rating were 1000 kW, then a Prime Power rating might be 850 kW, and the Continuous Rating 800 kW. However these ratings vary according to manufacturer and should be taken from the manufacturer's data sheet.
Often a set might be given all three ratings stamped on the data plate, but sometimes it may have only a standby rating, or only a prime rating.
Typical application - emergency power plant in hospitals, offices, factories etc. Not connected to grid.
Prime (Unlimited Running Time) Rating based on: Applicable for supplying power in lieu of commercially purchased power. Prime power is the maximum power available at a variable load for an unlimited number of hours. A 10% overload capability is available for limited time. (Equivalent to Prime Power in accordance with ISO8528 and Overload Power in accordance with ISO3046, AS2789, DIN6271, and BS5514). This rating is not applicable to all generator set models.
Typical application - where the generator is the sole source of power for say a remote mining or construction site, fairground, festival etc.
Base Load (Continuous) Rating based on: Applicable for supplying power continuously to a constant load up to the full output rating for unlimited hours. No sustained overload capability is available for this rating. Consult authorized distributor for rating. (Equivalent to Continuous Power in accordance with ISO8528, ISO3046, AS2789, DIN6271, and BS5514). This rating is not applicable to all generator set models
Typical application - a generator running a continuous unvarying load, or paralleled with the mains and continuously feeding power at the maximum permissible level 8760 hours per year. This also applies to sets used for peak shaving /grid support even though this may only occur for say 200 hour per year.
As an example if in a particular set the Standby Rating were 1000 kW, then a Prime Power rating might be 850 kW, and the Continuous Rating 800 kW. However these ratings vary according to manufacturer and should be taken from the manufacturer's data sheet.
Often a set might be given all three ratings stamped on the data plate, but sometimes it may have only a standby rating, or only a prime rating.
Typical operating costs
Fuel consumption is the major portion of diesel plant owning and operating cost for power applications, whereas capital cost is the primary concern for backup generators. Specific consumption varies, but a modern diesel plant will consume between 0.28 and 0.4 litres[5][6] of fuel per kilowatt hour at the generator terminals.
However diesel engines can operate on a variety of different fuels, depending on configuration, though the eponymous diesel fuel derived from crude oil is most common. The engines can work with the full spectrum of crude oil distillates, from natural gas, alcohols, gasoline, wood gas to the fuel oils from diesel oil to residual fuels.[7] This is implemented by introducing gas with the intake air and using a small amount of diesel fuel for ignition. Conversion to 100% diesel fuel operation can be achieveved instantaneously.[8]
* Fuel cost 11p - 16p/kWh (using red diesel at 40p/litre)
* lifetime engine maintenance about is 0.5p/kWh - 1.0/kWh
However diesel engines can operate on a variety of different fuels, depending on configuration, though the eponymous diesel fuel derived from crude oil is most common. The engines can work with the full spectrum of crude oil distillates, from natural gas, alcohols, gasoline, wood gas to the fuel oils from diesel oil to residual fuels.[7] This is implemented by introducing gas with the intake air and using a small amount of diesel fuel for ignition. Conversion to 100% diesel fuel operation can be achieveved instantaneously.[8]
* Fuel cost 11p - 16p/kWh (using red diesel at 40p/litre)
* lifetime engine maintenance about is 0.5p/kWh - 1.0/kWh
Typical costs of conversion to paralleling for grid operation
To be able to operate in parallel with the mains certain modifications are necessary which include the following:
* Approx. £3k to fit a PLC to the set
* Paralleling and synchronising gear and G59 equipment (this allows grid connection) Approx £5k
* Tidying up set (noise, larger fuel tank) Approx another £5k
* So for a 1MW set…£13/kW
* 50 kW…maybe £260/kW
This capital cost of £13/kW - £260/kW is low compared to combined cycle gas turbines that cost £350/kW
* Approx. £3k to fit a PLC to the set
* Paralleling and synchronising gear and G59 equipment (this allows grid connection) Approx £5k
* Tidying up set (noise, larger fuel tank) Approx another £5k
* So for a 1MW set…£13/kW
* 50 kW…maybe £260/kW
This capital cost of £13/kW - £260/kW is low compared to combined cycle gas turbines that cost £350/kW
Peak Shaving
Maximum demand tariffs in many areas encourage the use of diesels to come on at times of maximum demand. In Europe this is typically on winter weekdays around tea time (3 pm), whereas in the United States this is often in the summer to meet the air conditioning load.
Grid support
Emergency standby diesel generators such as those used in hospitals, water plant etc, are, as a secondary function, widely used in the US and the UK to support the respective national grids at times for a variety of reasons. In the UK for example, some 0.5 GWe of diesels are routinely used to support the National Grid, whose peak load is about 60 GW. These are sets in the size range 200 kW to 2 MW. This usually occurs during say the sudden loss of a large conventional plant of say 660 MW, or a sudden unexpected rise in power demand eroding the normal spinning reserve available.
This is extremely beneficial for both parties - the diesels have already been purchased for other reasons; but to be reliable need to be fully load tested. Grid paralleling is a convenient way of doing this.
In this way the UK National Grid can call on about 2 GW of plant which is up and running in parallel as quickly as two minutes in some cases. This is far quicker than a base load power station which can take 12 hours from cold, and faster than a gas turbine, which can take several minutes. Whilst diesels are very expensive in fuel terms, they are only used a few hundred hours per year in this duty, and their availability can prevent the need for base load station running inefficiently at part load continuously. The diesel fuel used is fuel that would have been used in testing anyway. See Control of the National Grid, National Grid Reserve Service[2][3]
A similar system operates in France known as EJP, where at times of grid extremis special tariffs can mobilize at least 5 GW of diesel generating sets to become available.In this case, the diesels prime function is to feed power into the grid
This is extremely beneficial for both parties - the diesels have already been purchased for other reasons; but to be reliable need to be fully load tested. Grid paralleling is a convenient way of doing this.
In this way the UK National Grid can call on about 2 GW of plant which is up and running in parallel as quickly as two minutes in some cases. This is far quicker than a base load power station which can take 12 hours from cold, and faster than a gas turbine, which can take several minutes. Whilst diesels are very expensive in fuel terms, they are only used a few hundred hours per year in this duty, and their availability can prevent the need for base load station running inefficiently at part load continuously. The diesel fuel used is fuel that would have been used in testing anyway. See Control of the National Grid, National Grid Reserve Service[2][3]
A similar system operates in France known as EJP, where at times of grid extremis special tariffs can mobilize at least 5 GW of diesel generating sets to become available.In this case, the diesels prime function is to feed power into the grid
Power plants - electrical "Island" mode
One or more diesel generators operating without a connection to an electrical grid are operating in "island" mode. Several parallel generators provides the advantages of redundancy and better efficiency at part loads. An island power plant intended for primary power source of an isolated community will often have at least three diesel generators, any two of which are rated to carry the required load. Groups of up to 20 are not uncommon.
Generators can be electrically connected together through the process of synchronization. Synchronization involves matching voltage, frequency and phase before connecting the generator to a live bus-bar. Failure to synchronize before connection could cause a high current short-circuit or wear and tear on the generator and/or its switchgear. The synchronization process can be done automatically by an auto-synchronizer module. The auto-synchronizer will read the voltage, frequency and phase parameters from the generator and bus-bar voltages, while regulating the speed through the engine governor or ECU (Engine Control Module). Typical manufacturers are ComAp, GAC, Woodward and Heinzman who dominate this market
Load can be shared among parallel running generators through load sharing. Like auto-synchronization, load sharing can be automated by using a load sharing module. The load sharing module will measure the load and frequency at the generator, while it constantly adjusts the engine fuel control to shift load to and from the remaining power sources. As the prime mover of a diesel generator runs at constant speed, it will take more load when the fuel supply to its combustion system is increased, while load is released if fuel supply is decreased.
Generators can be electrically connected together through the process of synchronization. Synchronization involves matching voltage, frequency and phase before connecting the generator to a live bus-bar. Failure to synchronize before connection could cause a high current short-circuit or wear and tear on the generator and/or its switchgear. The synchronization process can be done automatically by an auto-synchronizer module. The auto-synchronizer will read the voltage, frequency and phase parameters from the generator and bus-bar voltages, while regulating the speed through the engine governor or ECU (Engine Control Module). Typical manufacturers are ComAp, GAC, Woodward and Heinzman who dominate this market
Load can be shared among parallel running generators through load sharing. Like auto-synchronization, load sharing can be automated by using a load sharing module. The load sharing module will measure the load and frequency at the generator, while it constantly adjusts the engine fuel control to shift load to and from the remaining power sources. As the prime mover of a diesel generator runs at constant speed, it will take more load when the fuel supply to its combustion system is increased, while load is released if fuel supply is decreased.
Supporting main utility grids
In addition to their well known role as power supplies during power failures, diesel generator sets also routinely support main power grids worldwide in two distinct ways
Diesel generator set
The packaged combination of a diesel engine, a generator and various ancillary devices such as base, canopy, sound attenuation, control systems, circuit breakers, jacket water heaters, starting systems etc, is referred to as a generating set or a gen set for short.
While the larger industrial generators can range from 8 to 30 kVA for homes, small shops & offices up to 2,000 kVA used for large office complexes, factories. A 2,000 kVA set can be housed in a 40ft ISO container and be fully packaged and portable. Sizes up to about 5 MW are used for small power stations and these may use from one to 20 units. In these larger sizes the engine and generator are brought to site separately and assembled along with ancillary equipment
Diesel generators, sometimes as small as 250 kVA are widely used not only for emergency power, but also many have a secondary function of feeding power to utility grids either during peak periods, or periods when there is a shortage of large power generators.Ships often also employ diesel generators, sometimes not only to provide auxiliary power for lights, fans, and winches, etc. but also for main propulsion. With electric propulsion the generators can be placed in a convenient position, to allow more cargo to be carried. Electric drives for ships were developed prior to WW I. Electric drives were specified in many warships built during WW II because manufacturing capacity for large reduction gears was in short supply, compared to capacity for manufacture of electrical equipment. [1] Such a diesel-electric arrangement is also used in some very large land vehicles.
Generating sets are selected based on the load they are intended to supply power for, taking into account the type of load, ie emergency or for continuous power, and the size of the load, and size of any motors to be started which is normally the critical parameter.
While the larger industrial generators can range from 8 to 30 kVA for homes, small shops & offices up to 2,000 kVA used for large office complexes, factories. A 2,000 kVA set can be housed in a 40ft ISO container and be fully packaged and portable. Sizes up to about 5 MW are used for small power stations and these may use from one to 20 units. In these larger sizes the engine and generator are brought to site separately and assembled along with ancillary equipment
Diesel generators, sometimes as small as 250 kVA are widely used not only for emergency power, but also many have a secondary function of feeding power to utility grids either during peak periods, or periods when there is a shortage of large power generators.Ships often also employ diesel generators, sometimes not only to provide auxiliary power for lights, fans, and winches, etc. but also for main propulsion. With electric propulsion the generators can be placed in a convenient position, to allow more cargo to be carried. Electric drives for ships were developed prior to WW I. Electric drives were specified in many warships built during WW II because manufacturing capacity for large reduction gears was in short supply, compared to capacity for manufacture of electrical equipment. [1] Such a diesel-electric arrangement is also used in some very large land vehicles.
Generating sets are selected based on the load they are intended to supply power for, taking into account the type of load, ie emergency or for continuous power, and the size of the load, and size of any motors to be started which is normally the critical parameter.
Application
Engine-generators are used to supply electrical power in places where utility (central station) power is not available, or where power is needed only temporarily. Small generators are sometimes used to supply power tools at construction sites. Trailer-mounted generators supply power for temporary installations of lighting, sound amplification systems, amusement rides etc.
Standby power generators are permanently installed and kept ready to supply power to critical loads during temporary interruptions of the utility power supply. Hospitals, communications service installations, data processing centers, sewage pumping stations and many other important facilities are equipped with standby power generators. Some standby power generators can automatically detect the loss of grid power, start the motor, run using fuel from a natural gas line, detect when grid power is restored, and then turn itself off -- with no human interaction. [1]
Privately-owned generators are especially popular in countries where grid power is undependable or unavailable. Trailer-mounted generators can be towed to disaster areas where grid power has been temporarily disrupted.
Standby power generators are permanently installed and kept ready to supply power to critical loads during temporary interruptions of the utility power supply. Hospitals, communications service installations, data processing centers, sewage pumping stations and many other important facilities are equipped with standby power generators. Some standby power generators can automatically detect the loss of grid power, start the motor, run using fuel from a natural gas line, detect when grid power is restored, and then turn itself off -- with no human interaction. [1]
Privately-owned generators are especially popular in countries where grid power is undependable or unavailable. Trailer-mounted generators can be towed to disaster areas where grid power has been temporarily disrupted.
Diesel generator
A diesel generator is the combination of a diesel engine with an electrical generator (often called an alternator) to generate electric energy. Diesel generating sets are used in places without connection to the power grid or as emergency power-supply if the grid fails. Small portable diesel generators range from about 1 kVA to 10 kVA may be used as power supplies on construction sites, or as auxiliary power for vehicles such as mobile homes.
Types
Engine-generators are available in a wide range of power ratings. These include small, hand-portable units that can supply several hundred watts of power, hand-cart mounted units, as pictured below, that can supply several thousand watts and stationary or trailer-mounted units that can supply over a million watts. Regardless of the size, generators may run on gasoline, diesel, natural gas, propane, bio-diesel, sewage gas or hydrogen. Most of the smaller units are usually built to use gasoline (petrol) as a fuel, and the larger ones have various fuel types, including diesel, natural gas and propane (liquid or gas). Some engines may also operate on diesel and gas simultaneously (bi-fuel operation).
Some engine-generators use a turbine as the engine, such as the industrial gas turbines used in peaking power plants and the microturbines used in some hybrid electric buses.
Other engine-generators use a steam engine, such as most coal-powered fossil-fuel power plants.
Other engine-generators use a reciprocating engine.
The generator voltage (volts), frequency (Hz) and power (watts) ratings are selected to suit the load that will be connected.
Engine driven generators fueled on natural gas fuel often form the heart of small scale less than 1,000 kW combined heat and power installations.
There are only a few portable three-phase generator models available in the US. Most of the portable units available are single phase power only and most of the three-phase generators manufactured are large industrial type generators. In other countries where three-phase power is more common in households, portable generators are available from a few kW and upwards.
Portable engine-generators may require an external power conditioner to safely operate some types of electronic equipment. Small portable generators may use an inverter. Inverter models can run at slower RPMs to generate the power that is necessary, thus reducing the noise of the engine and making it more fuel-efficient. Inverter generators are best to power sensitive electronic devices such as computers and lights that use a ballast
Some engine-generators use a turbine as the engine, such as the industrial gas turbines used in peaking power plants and the microturbines used in some hybrid electric buses.
Other engine-generators use a steam engine, such as most coal-powered fossil-fuel power plants.
Other engine-generators use a reciprocating engine.
The generator voltage (volts), frequency (Hz) and power (watts) ratings are selected to suit the load that will be connected.
Engine driven generators fueled on natural gas fuel often form the heart of small scale less than 1,000 kW combined heat and power installations.
There are only a few portable three-phase generator models available in the US. Most of the portable units available are single phase power only and most of the three-phase generators manufactured are large industrial type generators. In other countries where three-phase power is more common in households, portable generators are available from a few kW and upwards.
Portable engine-generators may require an external power conditioner to safely operate some types of electronic equipment. Small portable generators may use an inverter. Inverter models can run at slower RPMs to generate the power that is necessary, thus reducing the noise of the engine and making it more fuel-efficient. Inverter generators are best to power sensitive electronic devices such as computers and lights that use a ballast
Mid-size stationary engine-generator
The mid-size stationary engine-generator pictured here is a 100 kVA set which produces 415 V at around 110 A per phase. It is powered by a 6.7 liter turbocharged Perkins Phaser 1000 Series engine, and consumes approximately 27 liters of fuel an hour, on a 400 liter tank. Diesel engines in the UK can run on red diesel and rotate at 1,500 or 3,000 rpm. This produces power at a frequency of 50 Hz, which is the frequency used in the UK. In areas where the power frequency is 60 Hz (United States), generators rotate at 1,800 rpm or another divisor of 3600. Diesel engine-generator sets operated at their peak efficiency point can produce between 3 and 4 kilowatthours of electrical energy for each liter of diesel fuel consumed, with lower efficiency at part load.
Components
In addition to the engine and generator, engine-generators generally include a fuel supply, a constant engine speed regulator (governor) and a generator voltage regulator, cooling and exhaust systems, and lubrication system. Units larger than about 1 kW rating often have a battery and electric starter motor; very large units may start with compressed air either to an air driven starter motor or introduced directly to the engine cylinders to initiate engine rotation. Standby power generating units often include an automatic starting system and a transfer switch to disconnect the load from the utility power source when there is a power failure and connect it to the generator.
Engine-generator
An engine-generator is the combination of an electrical generator and an engine (prime mover) mounted together to form a single piece of equipment. This combination is also called an engine-generator set or a gen-set. In many contexts, the engine is taken for granted and the combined unit is simply called a generator.
Voltaic Generator

The Voltaic Generator is the first solar bag powerful enough to charge a laptop. This solar laptop charger has high-efficiency cells and includes a battery pack custom designed to efficiently store and convert the electricity generated. It will also charge cell phones and most other hand held electronics.
* Solar panel generates up to 15 watts using 20% efficient cells, enough to fully charge the Voltaic battery in about 5 hours.
* The included battery pack stores the equivalent of a typical laptop charge and automatically delivers the required output voltages
* Common adaptors are included for connection to laptops, phones and other handheld devices. Optional reconfigured MagSafe adapter available for MacBooks.
* Or connect via USB or car charger
* Fabrics made from recycled PET (soda bottles), which is tough and water resistant
Equivalent circuit

The equivalent circuit of a generator and load is shown in the diagram to the right. To determine the generator's VG and RG parameters, follow this procedure: -
* Before starting the generator, measure the resistance across its terminals using an ohmmeter. This is its DC internal resistance RGDC.
* Start the generator. Before connecting the load RL, measure the voltage across the generator's terminals. This is the open-circuit voltage VG.
* Connect the load as shown in the diagram, and measure the voltage across it with the generator running. This is the on-load voltage VL.
* Measure the load resistance RL, if you don't already know it.
* Calculate the generator's AC internal resistance RGAC from the following formula:
R_{GAC} = {R_L} \left( {{{V_G}\over{V_L}}-1} \right)
Note 1: The AC internal resistance of the generator when running is generally slightly higher than its DC resistance when idle. The above procedure allows you to measure both values. For rough calculations, you can omit the measurement of RGAC and assume that RGAC and RGDC are equal.
Note 2: If the generator is an AC type, use an AC voltmeter for the voltage measurements.
The maximum power theorem states that the maximum power can be obtained from the generator by making the resistance of the load equal to that of the generator. This is inefficient since half the power is wasted in the generator's internal resistance; practical electric power generators operate with load resistance much higher than internal resistance, so the efficiency is greater.
Excitation

An electric generator or electric motor that uses field coils rather than permanent magnets will require a current flow to be present in the field coils for the device to be able to work. If the field coils are not powered, the rotor in a generator can spin without producing any usable electrical energy, while the rotor of a motor may not spin at all. Very large power station generators often utilize a separate smaller generator to excite the field coils of the larger.
In the event of a severe widespread power outage where islanding of power stations has occurred, the stations may need to perform a black start to excite the fields of their largest generators, in order to restore customer power service.
Terminology

The two main parts of a generator or motor can be described in either mechanical or electrical terms[citation needed]:
Mechanical:
* Rotor: The rotating part of an alternator, generator, dynamo or motor.
* Stator: The stationary part of an alternator, generator, dynamo or motor.
Electrical:
* Armature: The power-producing component of an alternator, generator, dynamo or motor. In a generator, alternator, or dynamo the armature windings generate the electrical current. The armature can be on either the rotor or the stator.
* Field: The magnetic field component of an alternator, generator, dynamo or motor. The magnetic field of the dynamo or alternator can be provided by either electromagnets or permanent magnets mounted on either the rotor or the stator. (For a more technical discussion, refer to the Field coil article.)
Because power transferred into the field circuit is much less than in the armature circuit, AC generators nearly always have the field winding on the rotor and the stator as the armature winding. Only a small amount of field current must be transferred to the moving rotor, using slip rings. Direct current machines necessarily have the commutator on the rotating shaft, so the armature winding is on the rotor of the machine.
MHD generator

A magnetohydrodynamic generator directly extracts electric power from moving hot gases through a magnetic field, without the use of rotating electromagnetic machinery. MHD generators were originally developed because the output of a plasma MHD generator is a flame, well able to heat the boilers of a steam power plant. The first practical design was the AVCO Mk. 25, developed in 1965. The U.S. government funded substantial development, culminating in a 25MW demonstration plant in 1987. In the Soviet Union from 1972 until the late 1980s, the MHD plant U 25 was in regular commercial operation on the Moscow power system with a rating of 25 MW, the largest MHD plant rating in the world at that time. [1] MHD generators operated as a topping cycle are currently (2007) less efficient than combined-cycle gas turbines.
Other rotating electromagnetic generators

Without a commutator, the dynamo is an example of an alternator, which is a synchronous singly-fed generator. With an electromechanical commutator, the dynamo is a classical direct current (DC) generator. The alternator must always operate at a constant speed that is precisely synchronized to the electrical frequency of the power grid for non-destructive operation. The DC generator can operate at any speed within mechanical limits but always outputs a direct current waveform.
Other types of generators, such as the asynchronous or induction singly-fed generator, the doubly-fed generator, or the brushless wound-rotor doubly-fed generator, do not incorporate permanent magnets or field windings (i.e, electromagnets) that establish a constant magnetic field, and as a result, are seeing success in variable speed constant frequency applications, such as wind turbines or other renewable energy technologies.
The full output performance of any generator can be optimized with electronic control but only the doubly-fed generators or the brushless wound-rotor doubly-fed generator incorporate electronic control with power ratings that are substantially less than the power output of the generator under control, which by itself offer cost, reliability and efficiency benefits.
Dynamo

The Dynamo was the first electrical generator capable of delivering power for industry. The dynamo uses electromagnetic principles to convert mechanical rotation into a pulsing direct electric current through the use of a commutator. The first dynamo was built by Hippolyte Pixii in 1832.
Through a series of accidental discoveries, the dynamo became the source of many later inventions, including the DC electric motor, the AC alternator, the AC synchronous motor, and the rotary converter.
A dynamo machine consists of a stationary structure, which provides a constant magnetic field, and a set of rotating windings which turn within that field. On small machines the constant magnetic field may be provided by one or more permanent magnets; larger machines have the constant magnetic field provided by one or more electromagnets, which are usually called field coils.
Large power generation dynamos are now rarely seen due to the now nearly universal use of alternating current for power distribution and solid state electronic AC to DC power conversion. But before the principles of AC were discovered, very large direct-current dynamos were the only means of power generation and distribution. Now power generation dynamos are mostly a curiosity.
Faraday's disk

In 1831-1832 Michael Faraday discovered the operating principle of electromagnetic generators. The principle, later called Faraday's law, is that a potential difference is generated between the ends of an electrical conductor that moves perpendicular to a magnetic field. He also built the first electromagnetic generator, called the 'Faraday disc', a type of homopolar generator, using a copper disc rotating between the poles of a horseshoe magnet. It produced a small DC voltage, and large amounts of current.
This design was inefficient due to self-cancelling counterflows of current in regions not under the influence of the magnetic field. While current flow was induced directly underneath the magnet, the current would circulate backwards in regions outside the influence of the magnetic field. This counterflow limits the power output to the pickup wires, and induces waste heating of the copper disc. Later homopolar generators would solve this problem by using an array of magnets arranged around the disc perimeter to maintain a steady field effect in one current-flow direction.
Another disadvantage was that the output voltage was very low, due to the single current path through the magnetic flux. Experimenters found that using multiple turns of wire in a coil could produce higher more useful voltages. Since the output voltage is proportional to the number of turns, generators could be easily designed to produce any desired voltage by varying the number of turns. Wire windings became a basic feature of all subsequent generator designs.
However, recent advances (rare earth magnets) have made possible homo-polar motors with the magnets on the rotor, which should offer many advantages to older designs.
Historic developments
Before the connection between magnetism and electricity was discovered, electrostatic generators were invented that used electrostatic principles. These generated very high voltages and low currents. They operated by using moving electrically charged belts, plates and disks to carry charge to a high potential electrode. The charge was generated using either of two mechanisms:
* Electrostatic induction
* The triboelectric effect, where the contact between two insulators leaves them charged.
Because of their inefficiency and the difficulty of insulating machines producing very high voltages, electrostatic generators had low power ratings and were never used for generation of commercially-significant quantities of electric power. The Wimshurst machine and Van de Graaff generator are examples of these machines that have survived.
* Electrostatic induction
* The triboelectric effect, where the contact between two insulators leaves them charged.
Because of their inefficiency and the difficulty of insulating machines producing very high voltages, electrostatic generators had low power ratings and were never used for generation of commercially-significant quantities of electric power. The Wimshurst machine and Van de Graaff generator are examples of these machines that have survived.
Electrical generator
In electricity generation, an electrical generator is a device that converts mechanical energy to electrical energy, generally using electromagnetic induction. The reverse conversion of electrical energy into mechanical energy is done by a motor; motors and generators have many similarities. A generator forces electric charges to move through an external electrical circuit, but it does not create electricity or charge, which is already present in the wire of its windings. It is somewhat analogous to a water pump, which creates a flow of water but does not create the water inside. The source of mechanical energy may be a reciprocating or turbine steam engine, water falling through a turbine or waterwheel, an internal combustion engine, a wind turbine, a hand crank, compressed air or any other source of mechanical energy.